9752 Installation Guide 3. Installation
11976870 Page 27
Programming Outputs
Control unit panel outputs can be programmed using the commands shown in
the table below. Open collector outputs are of a "pull down" type that provides
negative-applied control signals; the system adjusts the output polarity when
you select the output type.
Output Type Command
OP1 voltage-free relay 81
OP2 voltage-free relay 82
OP3 open collector 83
Figure 20 shows some examples of applications for open collector outputs
(OP3 is used in these examples).
OP3
+ve 12V Aux
Shock Sensor Reset
Use Command 83 4
VIPER
+ve
0V
OP3
+ve 12V Aux
Bell Follow Buzzer/Relay
Use Command 83 0
Relay energises/buzzer sounds
when bell activates.
BUZZER/RELAY
OP3
PIR Set Latch/Walk Test
For:
Set Latch use Command 83 3
Walk Test use Command 83 5
PIR
Figure 20. Wiring Examples for Open Collector Outputs
Wiring Keyswitches
To allow a user to set and unset the system using a keyswitch, connect a
fixed position or spring loaded (momentary) key switch to a zone input. When
programming the control unit select zone type (KM) for momentary or (KF) for
fixed position keyswitches. See Command 185 for keyswitch auto-reset.
Figure 21 shows the connections for a keyswitch.