LEDs
The LEDs (see Figure 2) have the following meanings:
LED1 (heartbeat) – Flashes once per second to
indicate that the panel is operating. The LED
flashes rapidly after a reset.
LED2 (network 1 fuse) – Monitors the polyfuse for
network 1. When illuminated, the LED indicates
that the 12V supply to network 1 is open circuit.
LED3 (network 2 fuse) – Same as LED2, but for
network 2.
LED4 (PSTN) – Illuminates when there is activity on
the PSTN port.
LED5 (power) – Illuminates when the panel is
energised (either from the AC input or from the
battery).
LED6 (12V output fuse) – Monitors the polyfuse
protecting the 12Vdc output from the terminal
block labelled "16" on Figure 2.
LED7 (Bell output fuse) – Monitors the polyfuse
protecting the bell output labelled "9" on Figure 2.
LED8 (relay 1 status) – Illuminates when relay 1 is
energised.
LED9 (relay 2 status) – Illuminates when relay 2 is
energised.
LED10 (transistor output 3 status) – Illuminates
when transistor output 3 is active.
LED11 (transistor output 4 status) – Illuminates
when transistor output 4 is active.
LED12 (strobe output status) – Illuminates when
the strobe output is active.
LED13 (bell output status) – Illuminates when the
bell output is active.
LED14 (transistor output 5 status) – Illuminates
when transistor output 5 is active.
Polyfuses
The PCB contains the following automatically-
resettable polyfuses. Note that to reset a polyfuse, the
load must be removed completely.
F1 – Battery load circuit (the on-board circuit that
periodically monitors the health of the battery).
F2 – Network 1 12Vdc output.
F3 – Network 2 12Vdc output.
F4 – Extension loudspeaker.
F5 – 12Vdc output from the 12V terminals on the
terminal block labelled "16" on Figure 2.
F6 – Bell output on the terminal block labelled "9"
on Figure 2.
Electromagnetic Compatibility
When used as intended this product complies with
EMC Directive (89 /336 /EEC). Any modifications other
than those stated in this manual, or any other use of
this product may cause interference and it is the
responsibility of the installer to comply with the EMC
and Low Voltage Directives.
Technical Specifications
Environmental Class II
Security EN50131-1 or PD6662 Grade 1, 2
or 3. See page 14.
Mains Supply: 145mA @ 230Vac±10%, 50Hz
PCB Power Supply: 13.65VDC, 1.5A
A maximum of 750mA is available
for the control panel PCB and
other devices (excluding battery
recharge)
Standby Battery: 12VDC, lead-acid.
See page 14 for further details.
Charging limit: 750mA
Recharge time: 24 hrs max. for 17AH battery
Zones: 8 on-board zones, expandable to
264
Network 1 or 2: Max of 16
MSNodes/MRNodes/MSPSUs, 5
keypads/LEC2s, 4 MIDNodes, or 2
IDNodes per network
Additional ports: Engineer's keypad port
USB and RS232 ports to PC
Printer (RS232) port
PSTN/RJ11 for phone connection
Output module port
Relay Outputs: 2 voltage-free changeover
1A max @ 24Vac or 24Vdc
Transistor Outputs: 2 Switched -ve @500mA
1 Switched +ve @500mA
Digi Outputs 1-16: Source 5mA in 12V condition
Sink 100mA in 0V condition
Selectable output sense
REN Value: 0.2
Speaker Output: 16 Ohms
Bell Trigger: Switched -ve @500mA
Strobe Trigger: Switched -ve @500mA
Mains Input Fuse: T315mA 250V 20mm
Dimensions: 384(W), 312(H), 95(D) mm
Material: 1.2mm mild steel
Weight: 4.9 Kg
Environment: -10 to 40°C
Humidity 0 to 75% RH, non-condensing.