9651 Programming
11772232 Page 31
Leaving Installer Mode
When you have finished programming the control unit:
1. Press 99y at the keypad
The display shows:
99:Exit Eng ?
2. Press y.
The display shows:
99:Checking Sys
followed by the time and date.
The system is now in user mode.
Note: If any 24-hour, Fire, PA or Technical zones are active when you enter
Command 99, the keypad gives an error tone and displays the faults.
Correct the problems identified. When the display shows "No Faults",
press
y
to enter user mode.
Restoring Default Access Codes (first stage reset)
The default (original) access codes are:
4-digit 6-digit
Engineer Code 7890 567890
Access Code User 1 1234 123456
Access Code Users 2 to 50
X002 ... X050 X00002 ... X00050
Duress Code
X051 X00051
Note: To activate the Access Codes (02 to 50) and Duress Code, which are
initially inactive, User 1 must change the defaults to the correct codes.
The 9651 User Guide explains how to do this.
To restore all access codes to their default settings:
1. Remove mains power.
2. Open the case and disconnect the battery.
3. Identify the NVM Reset pins and Kick Start pins on the main PCB (refer
to Chapter 3).
4. Short circuit the NVM Reset pins with a wire link.
5. Short circuit the Kick Start pins with a wire link.
6. Reconnect the battery.
7. Remove the wire links from the NVM Reset pins and Kick Start pins.
The control unit will load the factory default access codes listed above.
8. Close the control unit.
9. Apply mains power.
10. Carry out an engineer reset (see next section).