4. Programming
76 496792
If the keypad display shows “Custom” when you enter Command 143 then
<Downloader> has been used to program this Command.
Plug by Communicator Outputs (Commands 151 to 158)
The main circuit board of the control unit provides eight programmable
outputs that can be used to control a plug-by communicator. The outputs can
be connected to the communicator by an twelve-way wiring harness provided
with the control unit. See “3. Installation - Fitting a Plug-by Communicator” for
details of the wiring harness.
Commands 151 to 158 allow you to assign one of several channels to each
output. Command 151 controls output 1, 152 output 2, and so on up to
Command 158 which controls output 8. Each Command has the same
options, as follows:
00 Not used 11 AC Fail
01 Fire 12 Tamper Alarm (Day tamper)
02 PA 13 Open
03 Burglar 14 Close
04 Open/Close 15 Zone Omitted
05 Alarm Abort 16 Medical Assistance
06 Technical Alarm 17 Key Box
07 Alarm Confirmation 18 Anti Mask
08 RF Low Battery 19 Smoke Detector
09 Supervision Loss 20 Comms Acknowledge (See Note)
10 RF Jamming 21 Battery Fault
Note: 1. If the control unit is using Fast Format signalling, and has sent a Burg to the
ARC, then the control unit activates the output pin assigned to Comms Ac-
knowledge when the ARC returns a Comms Acknowledge signal. (Use Com-
mand 101 to enable comms.)
2. The control unit delays reporting/loging either mains loss, or exiting engi-
neering with mains loss, by 15-18 min (chosen randomly). If you chose a
Scandinavian default in Command 0 then the control unit waits at least 60
minutes before reporting.
Confirmation Timer (Command 160)
Note: Enable Alarm Confirmation (Command 89) to access this Command.
This Command controls a timer. The timer starts when an alarm is triggered
for the first time. If a second alarm is triggered before the timer expires then
the control unit transmits a confirmed alarm to the ARC. You can set the
timer to any value in minutes between 1 and 999. For DD243: 2002 compli-
ance set confirmation time to default (=30 mins).