i-on30EX
Page 13
Each loudspeaker draws up to 280mA in
operation. if there is more than one
expander loudspeaker then the bus may
not be able to supply sufficient current
during an alarm.
Step 5. Connect Control
Unit to Mains
WARNING: ENSURE THAT THE MAINS
SUPPLY IS DISCONNECTED AND ISOLATED
BEFORE MAKING ANY MAINS
CONNECTIONS. All mains electrical
connections must be carried out by a
qualified electrician and must comply with
the current local regulations (e.g. IEE).
Mains Cabling
Note: To avoid mains interference, the
mains cable must enter the control unit
through its own cable entry hole (7 in Fig 1)
and must not be mixed with other cables.
Mains Connection
Figure 15 shows the mains connection.
Connect to a suitable supply using a double
pole disconnect device in accordance with
EN60950-1.
Caution: Do not apply power at this
point.
Anchor the mains cable with a strain-relief
tie. There is a eye located near the mains
cable entry hole for this purpose (6 in Fig
1).
Figure 15 Mains Connection
Step 6. Connect Wired
Zones
The control unit and the wired expander
connectors can be used for either four wire
Closed Circuit Loop (CCL) detectors, or two
wire Fully Supervised Loop (FSL) detectors.
Four Wire Closed Circuit Connections
Figure 16 shows the wiring for CCL zones
on the control unit. Figure 17 shows the
wiring for CCL zones on the wired
expander. Note that the connections are
different on the expander compared to the
control unit.
Figure 16 Control Unit CCL Zone Wiring
Komentarze do niniejszej Instrukcji