4. Programming
496964 Page 61
Programming Command Reference
0: Country PTT Defaults
Use this command to select the country and PTT defaults; use Command 126
to select language. This Command also loads default access codes and
programming options.
Note: If you select options
X
4,
X
5,
X
6 or
X
7 (Finland, Norway, Sweden or
Denmark), the control unit also changes the method of entering
programming mode (see "Entering Programming Mode" on page 47).
Option Option Option
0 UK 6 Belgium
X3
OEM 2
1 Italy 7 Germany
X4
Finland
2 Spain 8 Switzerland
X5
Norway
3 Portugal 9 Austria
X6
Denmark
4 Netherlands
X1
Ireland
X7
Sweden
5 France
X2
OEM 1
01 to 16, X17 to X40: Zone Programming
The number of zones available to program depends on the control unit and
the number of expanders used in your system (see "Features" starting on
page 2). The format for the Command number changes, depending whether
the zone is connected to the control unit or to an expander. For the first 16
zones, key in "01" to "16" and press Y. For zones 17 upwards, which are
connected to expanders, key in "X17" to "X40" (if you have that many zones
connected) and then press Y.
Commands 01 to 40 take three or more digits. The first two digits specify the
zone type, while subsequent digits specify the zone attributes.
When you key in the zone number and press Y, the display shows the zone
number and any text caption for the zone. At this point, you can edit the zone
text as described below. When the text is as required, press Y to display the
type and attributes for the zone. At this point, you can edit them as described
below. When they are as required, press Y once more to store the changes.
Zone Names
When you key in the zone number and press Y, the display shows the current
zone name with a flashing cursor under the first letter. The system can store
up to 12 characters per name, including spaces and punctuation marks.