4. Programming
496964 Page 69
21: Zone Configuration
This Command allows you to select the wiring type of the zone connectors on
the main PCB.
9751/2
0 Closed Circuit Loop four-wire (CC 4 wire)
1 Fully Supervised Loop (FSL 2K2/4K7)
9851
0 Closed Circuit Loop four-wire (CC 4 wire)
1 End of Line resistor (EOL 2K2)
2 Fully Supervised Loop (FSL 2K2/4K7)
3 Eight Fully Supervised Loop plus four expanders (FSL + EXP)
You can connect more zones using expanders. The maximum number of
zones depends on the type of control unit. See "3. Installation" for details.
22: Loudspeaker Chime
In a single system, a user may find that the Chime tone from the keypads is
not loud enough. If so, use this Command to make the internal sounder give
the Chime tone as well. If you select option 0, the internal sounder emits no
tone. Select a value from 1 (quietest) to 9 (loudest) to set the Chime volume.
The internal sounder demonstrates the volume when you enter the digit.
23: Remote Reset
Option 1 enables Remote Reset, which is designed to operate with the plug-
by communicator or remote PC reset.
Note: You must set System Reset to Engineer (Command 33 option 1) and
program a CSID code (Command 50) to ensure Remote Reset works
correctly.
After an alarm, the user keys in their access code to silence the alarm but
cannot reset the system. The first alarm message to display and the Service
LED remains visible. The user contacts the ARC, which verifies the user's
identity and then sends a signal back to the control unit. The Service LED
goes out and the user can then reset the system with any valid access code,
providing that there are no faults.
Use option 0 (the default) to disable this function.