Cooper Security 9751 Podręcznik Użytkownika Strona 39

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 96
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 38
2. Programming Commands
497096, issue 3 Page 33
In a partitioned system, the options are:
Option
0 Timed. Use this option if Partition C sets after an exit time selected
using Command 75. If an Exit Terminate button is fitted, the user may
use it to shorten the exit time.
1 Terminate. Use this option if the user completes setting the partition
by pushing an Exit Terminate button connected to a keypad. The exit
time is infinite in this option.
2 Final Door Set. Use this option to complete setting the partition by
closing a door fitted with a Final Exit zone detector. The exit time is
infinite in this option.
3 Instant Set (no exit tone). Use this option to make the system set
without delay or exit tone.
4 Silent Set. Use this option to make the system set without an exit
tone. Use Command 75 to program the exit time.
5 Lock Set. See Command 39 on page 20 for an explanation.
73: Level/Partition C Alarm Response
This command sets the Alarm Response for Level or Partition C.
In a single system, the options are:
Option
0 Keypad sounders only.
1 Internal sounders and keypad sounders (default).
2 Local alarm (internal and external sounder only).
3 Full alarm (communication and internal/external sounders).
In a partitioned system, the options are:
Option
0 Keypad sounders only.
1 Local alarm (internal and external sounder only).
2 Full alarm (communication and internal/external sounders) (default).
Note: Compliance with PD 6662 / prEN 50131-1: 2004 (see page 85) requires that
Command 73 is set to option 2 in a partitioned system.
74: Not used
Level C Entry Time has been replaced by Command 201–204.
Przeglądanie stron 38
1 2 ... 34 35 36 37 38 39 40 41 42 43 44 ... 95 96

Komentarze do niniejszej Instrukcji

Brak uwag