2. Programming Commands
497096, issue 3 Page 47
114: Access Mode
You may wish to impose extra security on communication between a remote
PC and the control unit as, once the PC is connected, Downloader has
access to all programming commands. Select option 0 (the default) to require
the user to initiate communication with the remote PC. Select option 1 to
accept remote calls but check the details sent by the Downloader software.
Select option 2 if you do not require extra security.
Option
0 Callback off (Attended).
Operation: Someone must initiate a call to the remote PC manually
using Command 0 in User Mode. This command calls the first
Downloader Telephone Number (set with Command 118).
1 Callback on (Secure Callback).
Operation: When the remote PC calls, the control unit answers after a
set number of rings (set with Command 112). The control unit hangs
up and checks that the received control unit ID and software version
are correct. If they are, it waits for a short delay and then calls the PC
back using one of the Downloader Telephone Numbers programmed
with Commands 118 and 119 (see page 48).
2 Callback any (Unattended).
Operation: When unset, the control unit answers after a set number of
rings (set in Commands 112 or 113) and accepts programming
instructions immediately.
Notes:
1. Secure Callback must be disabled (default) until the first attended upload has been
performed. This first upload can be carried out either using Command 110, option 1
or using Command 114, option 0.
2. The Downloader operator can choose to use Secure Callback, even if the control
unit is programmed for Unattended.
115 and 116: Communicator Telephone Numbers
Use these commands to enter the telephone numbers to which the
communicator will report alarms. The numbers can contain up to 31 digits.
You can use the A key to insert a four-second pause, displayed as a comma
(,). When a number is successfully stored, the keypad gives a double "beep".
Use of the numbers depends on the setting of Command 101 (Call Mode):
° Option 0 (Disabled – default): the numbers are not used.
° Option 1 (Single): only the first number is used (Command 115).
° Option 2 or 3 (Alternate or Dual): both numbers are used.