Engineer Menu 2-6 Engineering Manual
122
Option 2-6: Setting Up Shunt Groups
Edit Shunt Grps
Group 02
Group 02 Zone >1
Zone ----
e.g.
[
Eng 2 Menu 6
Alter Shunt Grps
Group 02 Zone >2
Zone ----
Group 02 Zone 2
Zone >0001
Group 02 Zone 2
Zone >0002
Edit Shunt Grps
Group 01
[
|
[
[
|
|
e.g.
X
To view the next zone number
in the shunt group:
Pr e ss o r
to scroll, or
Press the hot key (1-8)
Press to save changes and continue
[
1 . SELEC T SHUN T
GROUP
2. SELECT THE ZONE
NUMBER TO EDIT
3 . SPEC I FY THE ZO N E
NUMBER
To specify the zone number to include in
the shunt group:
Pr e ss o r
r
to scroll, or
Press to c hoose zone on next network
(e.g. to change 0001 to 1001), or
Enter zone number (e.g. 0002)
e.g.
To select the shunt group:
Pr e ss o r
to scroll, or
Enter the shunt group number (e.g. 02)
Shows the zone number
alloc ated to this slot in the
g ro u p . "- - - -" m e a n s n o zo ne
number a llocated
There can be up to 8
zo n e s in t h e shun t g ro u p
If a zone num b er is displayed, you c an remove the
zone from the group by pressing , followed by
(or or ) while "> " is disp la yed on the top line.
r
]
Shunt groups provide a simple way to isolate zones until further notice.
Each shunt group can contain up to eight zones, and each group can be allocated to a user of
type "Shunt" (User option 2-4; see the
Manager's Manual
). When the user's code is first entered,
the zones are isolated. When the code is entered again, they are reinstated.
Although 24-hour zones are most commonly isolated, any zone can be assigned to a shunt
group.
)
Any zone selected must have the Shuntable attribute (page 29).
)
Reinstating zones may start the exit timer, depending on whether Unshunt, No Exit or
Unshunt & Exit is selected (page 87).