Engineering Manual Engineer Menu 1-4
45
014 – Active Omit
If a latching sensor (such as a door contact or break glass, but NOT a PIR) activates a zone,
and the zone remains active until the end of the confirmation time (page 62), the control
panel omits the active zone and triggers the Active Omit output. The control panel
deactivates the output when a user resets the system.
015 – Zones Omitted
Activates when any zone is omitted (e.g. by user option 1-2); deactivates when all zones
have the omits removed.
016 – 24 Hour Omitted
Activates when any 24 Hour zone is manually omitted; deactivates when all omitted zones
are reinstated.
017 – 24 Hour Alarm
Activates when any 24 Hour zone (page 22) goes into the alarm state if the panel is unset,
and deactivates when all 24 Hour alarms have been reset.
018 – Zones Shunted
Activates when any shunt group (page 122) is omitted; deactivates when the shunt group
is reinstated.
019 – Technical
Activates when any Technical zone (see page 23) triggers; deactivates when the alarms
have been reset.
020 – PSTN Line Fault
Activates when a line fault is detected between the on-board modem and the Alarm
Receiving Centre (ARC); deactivates when the telephone line is restored. The Line Fault
communications option (page 119) must be enabled for this output to activate when there
is a line fault.
021 – Panel Mains Power Off
Activates when the mains power is removed from the control panel; deactivates when the
mains power is restored.
)
The AC Off Delay timer (page 63) determines how long the mains must be off
before the output activates.
022 – Access Code
If the Access Code Only configuration option is set (page 87), this output activates when a
user code of type Access is entered. If the Access All Codes configuration is set (page 87),
this output activates when any valid user code is entered. The output deactivates one
second later if the output is latched, or for the length of the pulse if the output is pulsed.
023 – Soak Test Fail
Activates when any zone undergoing a "soak test" (page 28) triggers; deactivates when
reset by the engineer.