Engineering Manual Engineer Menu 1-1
29
6 – Masking
Use this attribute only if the zone is a three-resistor zone used to detect sensor masking.
Refer to page 26 for further information.
7 – Entry
Zones with this attribute start the Entry Delay timer (page 61) when the system is part set
(i.e. not all wards are set) and respond as normal when full set. This attribute must be
assigned to all zones that are required to start the Entry Delay timer in the part-set
condition.
Note: Do not use this attribute in software version 3.01.xx onwards. Please use an Entry zone
type and refer to Ward Attributes
1
-
3
-
2
option 16 (see page 38).
8 – Chime Tone 1
Zones with this attribute will cause the extension loudspeakers (connected to the control
panel) and keypad sounders to generate a single two-tone “chime” sound if chimes are
enabled for the zone's ward in User option 1-5 and the zone is triggered.
Chimes are generated at all keypad sounders and extension. However, using the Sndr Ctl
output type (page 56), you can make keypad sounders produce only those sounds that are
relevant to a specific ward.
If you select the Chime Visible configuration option (page 85), the keypad displays the
zone number when a chime occurs.
Setting this attribute to YES automatically sets Chime Tone 2 and Chime Tone 3 to NO.
The attribute can also be set using User option 2-5.
9 – Chime Tone 2
This is similar to Chime Tone 1, but a double two-tone “chime” sound is generated.
Setting this attribute to YES automatically sets Chime Tone 1 and Chime Tone 3 to NO.
Chime Tone 3
This is similar to Chime Tone 1, but a triple two-tone “chime” sound is generated.
Setting this attribute to YES automatically sets Chime Tone 1 and Chime Tone 2 to NO.
Inverted
By default, a zone is "triggered" by opening the zone contacts. If the zone's Inverted
attribute is set to YES, the zone triggers when the zone contacts close. Apply this attribute
when monitoring normally open devices such as exit terminator buttons or pressure pads.
Shuntable
Zones with this attribute are automatically shunted (Isolated) if:
A user chooses to shunt all zones in a selected ward using User option 1-3 (24 Hour
zones only).
A user code of type Shunt is entered at the keypad (as set up in User option 2-4).
A Shunt Key zone is triggered (page 24).