Engineer Menu 1-4 Engineering Manual
50
networks are not available. If a single-path communicator is used (which does not require
the ATS Test output from the panel), applying a constant +12Vdc to the LINE FLT input of
the panel generates an "ATE L.F. All" alert.
)
Invert the sense of the output at the panel if a "positive applied" input sense is
used at the communicator. The Normal/Pulsed output mode (page 59) is not used
for the ATS Test output type.
069 – Ready to Set
This output is intended for connection to a card or prox tag reader installed outside the
protected area. The output can be used to drive a “Ready to Set” led so that a user can see
the state of the system before attempting to arm it. The output is active when there are no
resets pending, all wards have all their zones closed, and no wards are set already.
070 – Auxiliary Fuse
Activates when the panel's auxiliary 12V fuse is blown.
If you want to use this event for a output that is powered by the panel, the output must be
configured so that its normal state is "on" to indicate the presence of power, and "off"
means power is off. If you are using a switched-negative digital communicator output, this
means that the sense of the output must be inverted. Note that the communicator must
be powered from a different source for the power failure to be communicated.
071 – Bell Fuse
Activates when the polyfuse protecting the bell output fuses.
072 – Network 1 Fuse
Activates when the polyfuse protecting the Network 1 output fuses. Do not use this event
for outputs connected to any device on network 1.
073 – Network 2 Fuse
Activates when the polyfuse protecting the Network 2 output fuses. Do not use this event
for outputs connected to any device on network 2.
074 to 079 – Always Off
This output never activates.
080 – Rem Batt Fault
This activates when there is battery fault at any MSPSU.
081 – Rem Mains Off
This activates when mains power switches off at any MSPSU.
082 – Rem Pwr Out Flt
This activates when the voltage from any MSPSU power supply is too high or too low. This
may indicate excessive loading (voltage too low).
083 – Sys Batt Fault
This activates when there is a fault with the battery in the control panel or any MSPSU.