Cooper Security M2000 Podręcznik Użytkownika Strona 31

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 30
Engineering Manual Engineer Menu 1-1
23
3 – PA Silent
This zone is monitored at all times. When triggered, it can activate outputs that follow the
Panic Alarm (page 44) or P.A. Alarm (page 54) event, but it does not cause an audible
alarm. It cannot be used to generate confirmed alarms (page 89).
4 – PA Audible
This is the same as the PA Silent zone type, but also generates a full alarm.
5 – Fire
A Fire zone is normally connected to a smoke detector that is monitored at all times.
When triggered, it generates a fire tone at keypads and at the panel's extension
loudspeaker (if fitted). It also activates the strobe and pulses the external bell output for
the Bell Duration time (page 61), providing it is not disabled by the Bell & Strobe attribute
(page 37).
See also the Unset Fire ward attribute (page 37) and Latching Fire configuration setting
(page 86).
6 – Technical
This zone is monitored at all times. When an event triggers the zone, the control unit
activates any outputs of type Technical (page 45) and sounds an alert tone at the keypads.
The user can reset the alert by entering their access code at a keypad.
7 – Final Exit
A Final Exit zone must be the first detector or door contact that is triggered when entering
the protected area. Once set, triggering this zone starts the ward Entry Delay timer (page
61).
)
While the Entry Delay timer is running, any Entry zone (page 24), or any zone that
has the Access attribute (page 28) set to YES does not cause an alarm.
)
The Entry Delay timer can also be started if the system is part set by triggering a
Normal Alm zone that has the Entry attribute (page 29) set to YES.
)
You may want to set the Access attribute for a Final Exit zone to YES to prevent the
keypad sounder from making a "zone in fault triggered" tone when the detector is
triggered.
If the setting mode is Final Exit or Exit Terminate (page 76), triggering the zone when
exiting the protected area affects when the panel sets the ward.
8 – Exit Term
An Exit Terminator zone is normally connected to a push button outside the protected
area, and is used as a positive confirmation that setting of the associated wards is
required. Depending on the setting mode (page 76), triggering an exit terminator may be
required before the panel can set the associated wards, or triggering exit terminator may
shorten the period for the wards to set.
An exit terminator zone type is not relevant for the entry procedure.
Przeglądanie stron 30
1 2 ... 26 27 28 29 30 31 32 33 34 35 36 ... 179 180

Komentarze do niniejszej Instrukcji

Brak uwag