Engineering Manual Engineer Menu 2-7
131
Option 2-7-3-6 – Viewing Network Errors
Network 2 0254
Last error 2,01
[
1234567890123456
1234567890123456
Equipment 6
Network Errors
Network 1 0003
|
1. SELECT NETWORK
Press when you have finished
]
]
e.g.
Erro r c o un t
La st e rro r
To select network:
Pre ss o r
to scroll, or
Enter network number (e.g. 2)
This option allows you to view the number of data transmission errors for each network.
)
You can re-set the error count to zero by pressing the 0 key. You may want to do this, then
use the option again (e.g. in 20 minutes) to determine the number of errors that are
occurring.
Transmission errors can be caused by poor terminations, intermittent cable faults, RF
interference, voltage drops, earth faults, cables for different networks routed together and
sounder cables routed with network cables. The system can operate with no ill effects with up to
20 errors in a 24-hour period.
Option 2-7-3-7 – Resetting User 1 (the default Manager User)
Equipment 7
Default User 1
[
[ENT] to DEFAULT
user code 1.
[
Press to c o nfirm reset
of user 1 passcode
[
This option allows you to reset user 01 (a Manager user) back to the factory default code of
5678, or 567800 (if 6-digit user codes are used; see page 91). The operation is logged.